R-(N)TSCGEWÖU

Medium Voltage rubber Flexible Cable for reeling Applications

  • Flexible cable designed for high mechanical stresses, especially for applications with frequent winding and unwinding with concurrent tensile and torsion stress. The cable is used for conveyors, container cranes,
  • Specially designed flexible reeling cable with optimised dimensions for extremely high mechanical stresses.
  • Occur in applications with monospiral reels and cylindrical reels, very high reeling speed, torsional stress.
  • Also for connection of large material handling machines such as excavators, dumpers, crushers in open-cast mines.
  • For use in wet or dry conditions, in industrial units, in underground and open-cast mining, in explosion-risk
  • areas.

Design Features

ConductorsAnnealed flexible stranded tinned or bare copper
conductor class 5 to IEC 60228.
Type of conductor design: opposite-lay with special
length of lay.
SeparatorSemi-conductive tape between the power
conductor and insulation and between earth
conductor and semi-conductive layer
Conductor screenSemi-conductive layer of special rubber
InsulationSemi-conductive, special strippable layer over
insulation of power cores. Maximum resistivity of
semi-conductive layers -200 [Ω x m]
Earth conductorTinned or bare copper conductor class 5 to IEC
60228 with extruded special semi-conductive
rubber compound
Core arrangementPower conductors and earth conductor (split into 3
parts) laid up around central semi-conductive filler.
Anti-adhesion graphite over assembled conductors
Inner sheathA special synthetic thermosetting compound type
5GM3 acc. to DIN VDE 0207/21, Red
Anti-torsion braidBraid of polyamide threads between inner and outer sheath
Outer sheathSpecial synthetic thermosetting compound, type
5GM5 acc. to DIN VDE 0207/21, Red

Features

Rated voltage3.6/6 6/10 8.7/15 12/20 kV
Max operating voltage7.2 12 18 24 kV
AC test voltage11 17 24 29 kV
Current carrying capacityDIN VDE 0298-4
Max conductor operating temperature+90°C
Max. conductor temperature during short circuit+250°C
Minimum ambient temperature for fixed installation-40°C
Minimum ambient temperature for mobile installation-25°C
Oil resistancePN-EN 60811-404, IEC 60811-404
UV resistanceUL 2556, ISO 4892-2
Twist limits100˚/m
Ozone resistantPN-ISO 1431-1
Travel speed180 m/min
Tensile load20 N/mm2
Flame propagationPN-EN 60332-1-2, IEC 60332-1-2

Technical Specifications

power Conductor Resistance